General specifications |
Signal type |
Digital Input |
Functional safety related parameters |
Safety Integrity Level (SIL) |
SIL 2 |
Systematic capability (SC) |
SC 3 |
Supply |
Connection |
Power Rail or terminals 9+, 10- |
Rated voltage |
19 ... 30 V DC |
Ripple |
≤ 10 % |
Rated current |
20 ... 15 mA |
Power dissipation |
≤ 700 mW including maximum power dissipation in the output |
Input |
Connection side |
field side |
Connection |
terminals 1+, 2- |
Rated values |
acc. to EN 60947-5-6 (NAMUR) |
Open circuit voltage/short-circuit current |
approx. 10 V DC / approx. 8 mA |
Switching point/switching hysteresis |
1.2 ... 2.1 mA / approx. 0.2 mA |
Line fault detection |
breakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA |
Pulse/Pause ratio |
min. 100 µs / min. 100 µs |
Output |
Connection side |
control side |
Connection |
output I: terminals 5, 6 ; output II: terminals 7, 8 |
Rated voltage |
30 V DC |
Rated current |
50 mA |
Response time |
≤ 200 µs |
Signal level |
1-signal: (external voltage) - 3 V max. for 50 mA
0-signal: blocked output (off-state current ≤ 10 µA) |
Output I |
signal ; Transistor |
Output II |
signal or fault message ; Transistor |
Collective error message |
Power Rail |
Transfer characteristics |
Switching frequency |
≤ 5 kHz |
Galvanic isolation |
Input/Output |
reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
Input/power supply |
reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
Output/power supply |
basic insulation according to EN 50178, rated insulation voltage 50 Veff |
Output/Output |
basic insulation according to EN 50178, rated insulation voltage 50 Veff |
Indicators/settings |
Display elements |
LEDs |
Control elements |
DIP switch |
Configuration |
via DIP switches |
Labeling |
space for labeling at the front |
Directive conformity |
Electromagnetic compatibility |
|
|
Directive 2014/30/EU |
EN 61326-1:2013 (industrial locations) |
Conformity |
Electromagnetic compatibility |
NE 21:2011 |
Degree of protection |
IEC 60529:2001 |
Protection against electrical shock |
IEC 61010-1:2010 |
Input |
EN 60947-5-6:2000 |
Ambient conditions |
Ambient temperature |
-20 ... 60 °C (-4 ... 140 °F)
extended ambient temperature range up to 70 °C (158 °F), refer to manual for necessary mounting conditions |
Mechanical specifications |
Degree of protection |
IP20 |
Connection |
screw terminals |
Mass |
approx. 100 g |
Dimensions |
12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch) (W x H x D) , housing type A2 |
Mounting |
on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas |
EU-type examination certificate |
BASEEFA 13 ATEX 0080 |
|
Marking |
II (1)G [Ex ia Ga] IIC
II (1)D [Ex ia Da] IIIC
I (M1) [Ex ia Ma] I |
|
Input |
Ex ia |
|
Voltage |
10.5 V |
|
Current |
17.1 mA |
|
Power |
45 mW (linear characteristic) |
Supply |
|
|
Maximum safe voltage |
253 V AC (Attention! Um is no rated voltage.) |
Output |
|
|
Maximum safe voltage |
253 V AC (Attention! The rated voltage can be lower.) |
Certificate |
CML 19 ATEX 4410 X |
|
Marking |
II 3G Ex ec IIC T4 Gc |
Galvanic isolation |
|
|
Input/Output |
safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
|
Input/power supply |
safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Directive conformity |
|
|
Directive 2014/34/EU |
EN IEC 60079-0:2018 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 |
International approvals |
UL approval |
|
|
Control drawing |
116-0374 (cULus) |
IECEx approval |
|
|
IECEx certificate |
IECEx BAS 13.0046
IECEx CML 19.0147X |
|
IECEx marking |
[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
Ex ec IIC T4 Gc |
General information |
Supplementary information |
Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |