Zener barriers provide cost saving Ex-protection for various applications in process automation systems. The amount of energy transferred to the hazardous location is limited to a safe level incapable of igniting the explosive atmosphere.
Z-system zener barriers from Pepperl+Fuchs are directly mounted on a 35 mm DIN-Rail. Through accessories, the required grounding can be done directly on the DIN mounting rail.
- Fast mounting on the DIN-rail
- Grounding directly connected with DIN-rail
- Separation of field loop by removing the fus
Z-system zener barriers are available with high density up to 2 channels / 12,5 mm width. Variants with field replaceable fuses provide a convenient means of disconnecting or open-circuiting the instrument loop without interfering with the wiring, making commissioning and maintenance operations much easier.
General specifications
|
|
|
1-channel, DC version, positive polarity, Working voltage 6.5 V at 10 µA, Series resistance max. 56 Ω, Fuse rating 100 mA, DIN rail mountable, Number of channels: 1-channel, Type: DC, positive, Working voltage: max. 8.5 V , 6.5 V at 10 µA |
Z710相關技術參數:
General specifications
Type DC version, positive polarity
Electrical specifications
Nominal resistance 50 Ω
Series resistance max. 56 Ω
Fuse rating 100 mA
Hazardous area connection
Connection terminals 1, 2
Safe area connection
Connection terminals 7, 8
Working voltage max. 8.5 V , 6.5 V at 10 µA
Conformity
Degree of protection IEC 60529
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Storage temperature -25 ... 70 °C (-13 ... 158 °F)
Mechanical specifications
Degree of protection IP20
Connection screw terminals , max. core cross-section 2 x 2.5 mm2
Mass approx. 150 g
Dimensions 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch)
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EC-Type Examination Certificate BAS 01 ATEX 7005
Group, category, type of protection II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C ≤ Tamb ≤ 60 °C) [circuit(s) in zone 0/1/2]
Statement of conformity TÜV 99 ATEX 1484 X
Group, category, type of protection, temperature class II 3G Ex nA IIC T4 Gc [device in zone 2]
Directive conformity
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approval
Control drawing 116-0118
UL approval
Control drawing 116-0139
CSA approval
Control drawing 116-0119
IECEx approval IECEx BAS 09.0142
Approved for [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Approved for [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
倍加福齊納式安全柵模塊產品型號參考:
Z705 Z779.F Z887 Z966.F
Z710 Z779.H Z888 Z966.H
Z713 Z779.H.F Z896 Z967
Z715.F Z786 Z905 Z978
Z722 Z787 Z910 Z040
Z728 Z787.F Z915 Z041
Z728.CL Z787.H Z915.1K Z042
Z728.F Z787.H.F Z928 Z810.CL
Z728.H Z788 Z954 Z813
Z728.H.F Z788.H Z955 Z857
Z731 Z788.R Z960 Z864
Z755 Z789 Z960.F Z865
Z757 Z796 Z961 Z865.F
Z764 Z810 Z961.F Z872
Z765 Z822 Z961.H Z879.F
Z765.F Z828.H.F Z964 Z879.H.F
Z772 Z878 Z965 Z886
Z778 Z888.H Z966 Z887.F
Z887.H.F Z922 Z715.1K Z715